| Technical specifications | |
|---|---|
| Detection angle | 120° |
| Sensing distance | maximum is 8 meters |
| Frequency Range | 5.725GHz-5.875GHz |
| Max. detection distance | 100 m |
| Features | |
| Installation | On the bottom there is a mounting slot for fastening the sensor with a plastic bracket. |
| Connection |
Motion sensor contains RJ-11 jack and is connected to an analog input of any system unit. Determination of sensor's type and connection occur automatically. To adjust sensitivity, read manual. To change cable connection, open the cover and read manual. |
| Supply includes |
Sensor, cable RJ11 4m, holder |
| Technical specifications | |
|---|---|
| Sensitivity | 0,05 - 0,2 db/m |
| Features | |
| Installation | On the bottom there are Ø5mm mounting holes for fastening the smoke sensor to the surface by 4.8×20mm screws or/and bracket and M4 screws. |
| Connection |
Detector's jack RJ-11 is connected to an analog input of any system unit using patch-cable RJ-11. Determination of the sensor's type and connection occur automatically. The monitoring system allows to connect several smoke detectors into a linear circuit. For this purpose each detector has two jacks RJ-11 input and output. The first is connected to an analog input of the system unit using a patch-cable RJ-11, the consequent is connected via patch-cable RJ-11 to an output of the first detector and so on. as one sensor with one address. |
| Supply includes |
Detector, 4-wired cable RJ11 (2m), 2 screws and 2 nuts M4, 2 screws 4.8×20mm, bracket, double sided sticker. |
| Net weight | 290g |
| Dimensions (LHW) | Ø100×45 |
| Max distance | 150m |
| Technical specifications | |
|---|---|
| Temperature range | -10… +80°C |
| Max. distance | 100 m |
| Connection | Connector RJ12 is connected to an analog input of any system unit. Determination of sensor's type and connection occur automatically. |
| Set includes |
Sensor, adapter, 4-wired cable RJ-12 (2m) |
| Net weight | 60g |
| Dimensions (LHW) | 60×18×18mm |
| Technical specifications | |
|---|---|
| Operating temperature | -10 ÷ 80°C |
| Accuracy | 1°C |
| Features | |
| Installation | On the bottom there is a ledge with Ø4.5mm and height 1mm and a Ø5mm mounting hole for fastening the sensor using a 4.8×16 mm screw. |
| Connection | Temperature sensor contains RJ-11 jack and is connected to an analog input of a system unit. Determination of type of sensor and connection occur automatically. |
| Supply includes |
Sensor, 4-wired patch cable RJ11 (2m), 4.8×16mm screw, double sided sticker. |
| Net weight | 50g |
| Dimensions (LHW) | 60×18×18mm |
| Max distance | 100m |
| Connection |
Can be connected via RJ-11 cable to each control unit. Determination of the sensor type and connection takes place automatically. At the end of the sensor, connect the 2-wire VT-WLC detection cable. |
|---|---|
| Maximum distance from the controller | 100m |
| The maximum length of the detection cable track | 225m |
| Set includes |
sensor, cable, terminal strip type TBW-5-2p, screw 4.8×16mm, double sided sticker, VT-WLC adapter |
| Net weight | 60g |
| Dimensions (LHW) | 60×18×18mm |
| Connection | The sensor is connected to the controller by the RJ-11 network cable. Determination of the sensor type and connection takes place automatically. Sensor response time 0.1s |
|---|---|
| Max. distance | 50m |
| Net weight | 106g |
| Dimensions | 60×18×18mm |
| Power Consumption | 60mW |
| Supply includes |
Sensor converter, airflow sensor, mounting bracket, 2m RJ11/RJ12 cable, screws, nuts, bolts and a sticker. |
| Technical specifications | |
|---|---|
| Measured temperature range | -10 ÷ 80°C |
| Accuracy | ±0.4°C in –10 to 85 °C range |
| Measured humidity range | 0 - 95%RH |
| Accuracy %RH | ± 3% RH in 0 to 80% range |
| Maximum distance from the appliance | 225m |
| Features | |
| Connection |
Sensor's jack RJ-12 is connected to CAN input of any system unit or to a CAN output of another sensor using RJ-12 patch cable. Determination of sensor's type and connection occur automatically. The system enables connecting multiple sensors to a linear layout. For this purpose, each sensor is equipped with two RJ-11 input and output sockets. |
| Net weight | 160g |
| Dimensions | 68 × 47 x 26 mm |
| Communications | |
|---|---|
| Sesnor type | CAN digital sensor |
| Inputs/Outputs | 2x RJ11 6p4c |
| Daisy chain |
Yes, a daisy chain is possible for all CAN sensors. |
| Max. distance from the monitoring unit | 225m |
| LED indicators | Red / Green (RUN/ERROR) |
| Accuracy | |
| Pressure RMS noise | 0.2Pa (equivalent to 1.7cm) |
| Pressure error | ±0.25% (equivalent to 1m at 400m height change) |
| Pressure from °C | ±1.5Pa/K (equivalent to ±12.6cm at 1 °C temperature change) |
| RH accuracy | ± 3% RH (max) |
| Hysteresis | ≤2% RH |
| Response time | 1s |
| Temperature | 1.5°C |
| Environmental | |
| Pressure range | 300 to 1100 hPa |
| Working temperature range | −40 to +85 °С |
| Humidity operating range | 0 to 95% RH |
| Power Requirement | |
| Power input |
12V DC, 1A (power supplied on a CAN bus chain) |
| Current consumption | 1 Watt |
| Mechanics | |
| Dimensions | 68x47x26 mm |
| Packaging weight | 160 g |
| Technical specifications | |
|---|---|
| Smoke sensitivity | 0,05 - 0,2 db/m |
| Response time | 10 sec |
| Measured temperature range | -10 to +75 °C |
| Accuracy | ±0.4°C in –10 to 85 °C range. |
| Measured humidity range | 0 - 95%. |
| Accuracy %RH | ± 3% RH in range of 0 - 80% |
| Maximum distance from the appliance | 225m |
| Features | |
| Installation | On the bottom there are mounting holes for fastening the smoke sensor to the surface using screws 4.8×20mm or/and bracket and M4 screws. |
| Connection | Sensor's jack RJ-12 is connected to CAN input of any system unit or to a CAN output of another sensor using RJ-11 patch cable. Determination of sensor's type and connection occur automatically. Monitoring system allows connection of up to 40 smoke sensors into a linear circuit. |
| Set includes |
Sensor, 3-wired shielded patch cable RJ11 (2m), bracket, 2 screws and 2 nuts M4, 2 screws 4.8×20mm, double sided sticker. |
| Net weight | 310g |
| Dimensions (LHW) | Ø100×45mm |
Page 3 of 8
|